Testing and Troubleshooting
151274-L8
10-4
A message similar to the one shown in Figure 10-2 will display.
Figure 10-2 Shut Down Warning
3.
Press the
or
arrow to toggle NO to YES then press
ENTER
.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4.
Select the SLC loop.
5.
Enter up to eight SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6.
Press
to exit SLC multi-locator function.
Note: Once you exit the system will resume normal operation.
10.3.3
I/O Point Control
This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a
point’s output mapping.
Follow these steps to control a I/O point:
1.
Select 2 (Point Functions) from the Main Menu.
2.
Select 6 (I/O Point Control).
3.
Select the Module the point is on.
4.
Enter the point number, or press the
or
arrow to select the point you wish to test, then press
ENTER
.
5.
Press
ENTER
to generate an alarm for an input point or activate an output point.
6.
To exit press
.