7

Table 2.D - DĆC MOTOR/CONTROLLER/TRANSFORMER SPECIFICATIONS

CONTROLLER

DĆC

OPTIONAL

POWER

TRANSFORMER

CONTROLLER

MODEL NUMBERS

AĆC

DĆC

DĆC

ARM.

DĆC

FIELD

AMP.

MAX

POWER

SUPPLY

MAXIMUM

kVA

FULL

LOAD

ENCLOSED CHASSIS HP VAC

A C

AMPS

(RMS)

D C

ARM.

(VOLTS)

ARM.

AMPS

(avg.)

FIELD

VOLTS

MAX.

(optional)

SUPPLY

CAPACITY

kVA

Per Phase

LOAD

kVA

14C30

14C40

1/4

1/3

1/2

3/4

115

115

115

115

ă3.5

ă5.2

ă7.0

10.5

ă90

ă90

ă90

ă90

ă2.5

ă3.7

ă5.0

ă7.5

100

100

100

100

3.0

3.0

3.0

3.0

1000

1000

1000

1000

40

40

40

40

ă0.75

ă0.75

1.0

1.5

14C31

14C41

1/2

3/4

1

1Ć1/2

230

230

230

230

ă3.5

ă5.2

ă7.0

10.5

180

180

180

180

ă2.5

ă3.7

ă5.0

ă7.5

200

200

200

200

3.0

3.0

3.0

3.0

1000

1000

1000

5000

40

40

40

40

ă1.0

ă1.5

ă2.0

ă3.0

14C32

14C42

2

3

230

230

14.0

21.0

180

180

10.0

15.0

200

200

3.0➀

3.0➀

5000

5000

40

40

ă5.0

ă5.0

14C33

14C43

5

230

35.0

180

25.0

200

3.0➀

5000

40

10.0

Standard

Maximum permissible available symmetrical RMS fault current.

Section 3

INSTALLATION

3.0 General Ċ This Section outlines the procedures that

are to be followed in order to properly plan, layout, asĆ

semble and install a Regenerative MinPak Plus controlĆ

ler.
The dĆc motor should be installed and wired in accorĆ

dance with installation instructions supplied with each

drive.
There are certain precautions that should be kept in mind

before planning begins. They should be considered a

general checklist which, if followed, will minimize installaĆ

tion problems and decrease assembly time. As a user

aid, they are listed here.

DANGER

THIS UNIT SHOULD BE INSTALLED, ADJUSTED

AND SERVICED BY QUALIFIED ELECTRICAL

MAINTENANCE PERSONNEL FAMILIAR WITH

THE CONSTRUCTION AND OPERATION OF

THIS TYPE OF EQUIPMENT. THEY SHOULD

ALSO BE FAMILIAR WITH THE POTENTIAL

HAZARDS INVOLVED. IF THIS WARNING IS NOT

OBSERVED, PERSONAL INJURY OR EQUIPĆ

MENT DAMAGE MAY RESULT.

DANGER

BE ABSOLUTELY CERTAIN THAT A GROUND

WIRE FROM THE INCOMING AĆC POWER LINE

IS PROPERLY CONNECTED TO THE CHASSIS

GROUND TERMINAL PROVIDED. WITHOUT

PROPER GROUNDING, PERSONAL INJURY

MAY OCCUR.

WARNING

THE USER IS RESPONSIBLE FOR CONFORMĆ

ING WITH THE NATIONAL ELECTRICAL CODE

WITH RESPECT TO MOTOR, CONTROLLER

AND OPERATOR DEVICE INSTALLATION, WIRĆ

ING AND STARTĆUP. THE USER IS ALSO REĆ

SPONSIBLE FOR UNDERSTANDING AND APĆ

PLYING ALL OTHER APPLICABLE LOCAL

CODES WHICH GOVERN SUCH PRACTICES AS

WIRING PROTECTION, GROUNDING. DISCONĆ

NECTS AND OVERCURRENT PROTECTION.

3.1 Planning, Layout Guidelines Ċ Before actualasĆ

sembly and installation begins, careful layout planning

must be made. This Paragraph lists recommended planĆ