Rockwell Automation MinPak Plus DC Drives Kits User Manual
Page 27

26
In cases where the Kit is secured by a mounting screw,
be sure to tighten it firmly but do not overtighten. ExcesĆ
sive force can strip the threads in the cast base.
6.1 Local Operator Faceplates Ċ When a Local OperĆ
ator Station is used with the Chassis Cover, one of five difĆ
ferent Chassis Faceplates must also be used. Each
Faceplate supports a number of selector switches and
potentiometers, as required by the specific application.
(Refer to Figure 6.2 and to Table 6.B for a list of FaceĆ
plates and related switches.)
The Faceplates are supplied with a bag of eight hex keps
nuts. The standard hex nut is used to secure the ground
wire. No other equipment nor any other Reliance Electric
options are required with this option.
NOTE: In cases where the Chassis is mounted without a
Cover. there is no need for a Faceplate. In this case, igĆ
nore these instructions.
It a Local Operator Station contains a AUTO/MANUAL
switch, it is necessary to remove jumper J4 from the RegĆ
ulator Module. (Refer to Figure 7.6.)
Table 6.A - MODIFICATION KIT QUICK REFERENCE LIST
KIT
MANUAL
PARAGRAPH
NUMBER
MODEL
NO.
CONTROLLER
MODIFICATION
?➀
ADDITIONAL
OPTIONS
REQUIRED
?
OPTIONS
REQUIRED
ADDITIONAL
USERĆ
SUPPLIED
PARTS?
Local Operator
Station
Faceplates
Blank Operator
Station
Faceplate
Remote
Operator
Adapter Kit
Auxiliary
M Contact
Voltage
Tachometer
Follower
Test Meter
Adapter
Field Supply ➂
Dynamic
Braking
Instrument
Interface/
Preset Speed
Master Isolated
Reference
Receiver
Dancer
Follower
6.1
6.2
6.2
6.7
6.4
6.8
6.6
6.3
6.5
6.9
6.10
14C202
14C204
14C206
14C208
14C200
14C220
14C219
14C223
14C225
14C228
14C214
thru 16
14C222
14C229
14C230
no
no
yes
no
yes
no
no
no
yes
yes
yes
no
yes
yes
no
no/yes
no
no
no
no/yes
no/yes
yes
no
None
D Reliance Remote
Operator Control Station
(Refer to Table 2.B.)
D Remote Operator
Adapter
(See Blank Faceplate, just
above.)
None
May need AUTO/MANUAL
selector switch
None
None
D If preset speed only, may
need AUTO/MANUAL
switch.
D If follows process
controller, May need
AUTO/MANUAL switch.
Master Isolated Reference
Transmitter
None
no
wire ➁
wire ➁
wire ➁ ➃
wire ➁
no
wire ➄
no
no
wire ➁
wire ➁
wire ➁
Dancer Pot and
optional Dancer
Position Pot
➀
Modification here means that some work such as jumper placement, resistor clipping, or wiring reconnection must be performed.
➁
Refer to Table 6.C.
➂
Supplied as standard with 2, 3 and 5 hp Regenerative MinPak Plus controllers.
➃
Not to exceed AWG No. 14.
➄
Refer to Paragraph 6.6 for specific sizes.