beautypg.com

Rockwell Automation MinPak Plus DC Drives Kits User Manual

Page 29

background image

28

Step 4 Ċ Locate the area on the Regulator Module

where the two connectors will connect. (Refer to Figure

4.2 or 7.6.) Note there are two sets of pins. Mate the conĆ

nector with the red wire in the end position connecting

to the pin marked 32 (RED). Mate the second connector

with the green wire in the end position connecting to the

pin marked 28 (GRN).
Step 5 Ċ Attach the ground (green) wire to the Auxiliary

Bracket mounting screw located halfway down the

hinged edge. (Refer to Figure 3.6.)
NOTE: For a Local Operator Control Station, no other

connections are necessary.
6.2 Remote Operator Station Ċ The optional Remote

Operator Adapter Kit allows the locating of operator

controls some distance from the Chassis.
In addition to a Remote Operator Adapter Module, this

Kit contains all the mounting hardware necessary to seĆ

cure the Module. (Refer to Figure 6.3.) However, one

may also need to order two additional options from ReĆ

liance Electric. (Refer to Paragraph 2.1.2.)

Figure 6.3 - Remote Adapter Kit

Step 1 Ċ Locate the area on the Regulator Module

where the Remote Operator Adapter Module is to be

mounted. Place the Module in the proper orientaĆ

tion: the edge with 10 holes should be aligned over

the 10 pins. (This area is marked RED 32 in Figure

7.6.) Carefully, slowly and gently press the Module

down on the pins until it bottoms out. Use the two

screws to secure it.
Step 2 Ċ Based on the specific control capability of the

Remote Operator Station chosen, select the required

wires specified in Table 6.C.
Step 3 Ċ Draw the wires into the Chassis through the

dedicated conduit. (Refer to Figure 3.7 ) Then cut indiĆ

vidual wires to lengths required for connection to the

kit's terminal strip. Wire according to Figure 3.8.

WARNING

WARNING EXCESSIVE LENGTHS OF BARE

WIRE COULD CAUSE SHORTS AND/OR

GROUNDS. STRIP MINIMAL INSULATION

FROM EACH WIRE.

Step 4 Ċ Visually inspect all wiring. Check wire placeĆ

ment against diagrams. Look for grounds and shorts

caused by broken insulation. Make sure the conduit is

grounded.
Step 5 Ċ Attach the blank Faceplate onto the Cover.

(Follow procedures outlined in Paragraph 6.1, Steps 1,

2, 3 but ignore the references to connectors.) Be sure to

attach the ground wire.
6.3 Dynamic Braking Ċ The standard Regenerative

MinPak Plus controller allows a drive motor to coast to

rest after the STOP switch is pressed. Optionally, a user

may install a Dynamic Braking Kit. (Refer to Figure 6.4.)

Its use allows a rapid, shockless stopping of the drive

motor.

Figure 6.4 - Dynamic Braking Kit

Dynamic Braking is not a mechanical holding brake. It

will not hold the shaft in place, nor will it prevent the motor

from turning once motion has stopped.
The Dynamic Braking option is actually a resistor conĆ

nected across the motor armature (Refer to Figure 7.3 in

which a schematic is shown.) It allows a motor to act as

a generator; the rotating mechanical (kinetic) energy is

converted into electrical energy that is dissipated in the

form of heat by the Dynamic Braking resistor. Note that

the resistor is sized for infrequent stops; thus, users must

allow time between stops for heat dissipation.
When ordering the Kit, it is necessary to specify Part

Numbers according to horsepower and voltage ratings.

(Refer to Table 8.A.)
The Dynamic Braking Kit contains the resistor and two

mounting screws. No other Reliance Electric options are

required, and no other userĆsupplied equipment is necĆ

essary.
To install the Kit, follow these procedures.
Step 1 Ċ It is easier to mount the Kit when the unit is in

a horizontal position, as is possible at initial installation.
Step 2 Ċ Remove the screws holding the Circuit Breaker

bracket. Move the assembly out of the way.
Step 3 Ċ Disconnect power leads A1 and A2 from 1TB;

disconnect leads 145 and 147 from the DV/DT Module;

disconnect the two current transformer feedback conĆ

nections (192, 193 and 292, 293, respectively) to the upĆ

per rightĆhand corner of the Regulator Module. Move the

assembly out of the way.