beautypg.com

Rockwell Automation MinPak Plus DC Drives Kits User Manual

Page 40

background image

39

SYMPTOM

PROBABLE CAUSE

RECOMMENDED PROCEDURES

1. POWER

ON/OFF

circuit

breaker on

controller

trips when

power is

Applied.

Incorrect wiring connecĆ

tions to controller, from

controller to motor. in moĆ

tor.

V Remove aĆc power at disconnect breaker.
V Remove leads to L1, L2, A1, A2 and. if used, F1, F2, on incoming side of

controller's 1TB, 2TB and 3TB. (Refer to Figure 3.8.)

V Put POWER ON/OFF circuit breaker in ON position.
V Check for a ground condition at L1/181, L2/182, A1, A2, F1 and F2. Do this at

controller (internal side of 1TB, 2TB and 3TB. If a ground is discovered,

check wiring connections on POWER ON/OFF circuit breaker. Also check

connection to Power Cube and motor field terminals F1 and F2.

V If no ground exists, examine the controller Chassis and Cover for loose wires

and/or foreign objects.

V If no ground exists and if no foreign objects are discovered, reconnect the

incoming conductors A1, A2 and, if used, F1 and F2. Then check for grounds

at these terminals.

V If a ground is found, it is in the conductors to the motor or in the motor itself.
V Disconnect the motor from the conductors at the drive motor.
V Test A1, A2, F1 and F2 conductors for a ground. (If one exists, examine

connections and insulation for areas where shorts could occur.)

V If no grounds are found in the conductors, check the motor for a ground

condition. If a ground is located here, examine and/or replace the motor, as

necessary.

Short in Power Cube.

V Replace Power Cube.

Short in Field

Supply Kit.

V Replace Diode Bridge in Field Supply Kit. Inspect wires and connections to

Field Supply Kit. Replace all damaged wires and connectors.

2. Drive motor

does not

start

Main aĆc line disconnect

not closed or fuse blown

or no power applied

ahead of disconnect

V Check disconnect switch, fuses in it, and voltage on line.

Drive interlocks preventing

operation.

V Verify that all userĆinstalled interlocks are in a state (physical condition and

wiring connections) to allow a start.

Drive motor thermostat

wires not connected on

controller terminals 32 and

132 on 2TB

V Check connections to thermostat: at drive motor P1, P2; at controller 32, 132.
V Check for open thermostat inside motor. Make a resistance check of

thermostat. (It should read a short, or low resistance, if it is closed.)

External overload wires

not connected on controlĆ

ler terminals 32 and 132

on 2TB.

V Check connections to external overload.
V Check for open overload. Make a resistance check to overload. (It should

read a short, or low resistance, if it is closed.)

DĆC circuit breaker (3CB)

open.

V Must open Cover to reset Check for motor ground conditions before

resetting.

DANGER

IF CIRCUIT BREAKER HAS TRIPPED, USER MUST REMOVE THE COVĆ

ER FROM THE DRIVE AND DETERMINE IF A FIELD SUPPLY KIT IS

PRESENT. (SEE FIGURE 4.5.) IF FIELD SUPPLY KIT IS PRESENT, THE

FIELD SUPPLY KITAND ITS WIRING MUSTBE INSPECTED FOR DAMĆ

AGE. AFTER CLOSING THE COVER AND REĆAPPLYING POWER TO THE

DRIVE, THE FIELD VOLTAGE MUST BE REĆCHECKED FOR PROPER

VOLTAGE AT MOTOR TERMINALS F1, F2. IF THIS VOLTAGE IS BELOW

90% OF THE FIELD VOLTAGE SPECIFIED ON THE MOTOR NAMEĆ

PLATE, THE DRIVE MUST NOT BE STARTED UNTIL PROPER VOLTAGE

IS OBTAINED. FAILURE TO FOLLOW THIS PROCEDURE COULD REĆ

SULT IN OVERSPEEDING THE MOTOR AND/OR THE MACHINERY

COUPLED TO THE MOTOR SHAFT AND POSSIBLE FATAL INJURY.