beautypg.com

Rockwell Automation MinPak Plus DC Drives Kits User Manual

Page 20

background image

19

Step 1 Ċ Attach one lead from the ohmmeter to the moĆ

tor frame to make a simple resistance check.
Step 2 Ċ Touch the test probe to each of the two power,

two thermostat, and two field leads to the motor. If the

reading to ground on any terminal is less than 100,000

ohms, a ground condition exists.
Step 3 Ċ If a ground condition exists, inspect the motor

thoroughly for internal shorts.
Step 4 Ċ When the grounding condition is corrected, reĆ

connect the conductors from the Regenerative MinPak

Plus controller.
4.3 Power On Adjustments Ċ Once all the preliminary

powerĆoff static adjustments have been performed with

acceptable results, the aĆc line power is to be applied to

the controller, but the load is not connected. It is imporĆ

tant to follow these steps closely. Observe all cautions

and warnings.
Note that these procedures progress on a cautious apĆ

proach. Under no circumstances should the sequence

be jumped to save time. Make sure each segment

checks out before moving on to another.
4.3.1 Preliminary Steps Ċ Assuming that all steps were

followed to this point, the following steps indicate how

the power may be applied to the controller.
Step 1 Ċ Close the Cover of the controller.
Step 2 Ċ On the Chassis Faceplate place the POWER

ON/OFF circuit breaker in the OFF position.
Step 3 Ċ On the Operator Station turn the SPEED and

TORQUE potentiometer, if used, to the zero position.
Step 4 Ċ Close the main aĆc disconnect. (Replace fuses

before closing the circuit, if necessary.)
Step 5 Ċ If no improper condition is observed, proceed

to the following Paragraphs.

DANGER

IF CIRCUIT BREAKER HAS TRIPPED, USER

MUST REMOVE THE COVER FROM THE DRIVE

AND DETERMINE IF A FIELD SUPPLY KIT IS

PRESENT. (SEE FIGURE 4.5.) IF FIELD SUPPLY

KIT IS PRESENT, THE FIELD SUPPLY KIT AND

ITS WIRING MUST BE INSPECTED FOR DAMĆ

AGE. AFTERCLOSING THE COVERAND REĆ

APPLYING POWERTO THE DRIVE, THE FIELD

VOLTAGE MUST BE REĆCHECKED FOR PROPĆ

ERVOLTAGE AT MOTORTERMINALS F1, F2. IF

THIS VOLTAGE IS BELOW 90% OF THE FIELD

VOLTAGE SPECIFIED ON THE MOTORNAMEĆ

PLATE, THE DRIVE MUST NOT BE STARTED

UNTIL PROPER VOLTAGE IS OBTAINED. FAILĆ

URE TO FOLLOW THIS PROCEDURE COULD

RESULT IN OVERSPEEDING THE MOTOR AND/

ORTHE MACHINERY COUPLED TO THE MOĆ

TORSHAFT AND POSSIBLE FATAL INJURY.

SEE PAGE 39 FOR TROUBLESHOOTING PROĆ

CEDURES.

4.3.2 Field Supply Check Ċ If the individual RegeneraĆ

tive MinPak Plus has an optional Field Supply Kit

installed, it must be checked while power is applied to

the unit. Since not all controllers have a Field Supply. it

must be determined if there is one before deciding

whether or not the check must be made. The following

controllers have a Field Supply:

D All controllers designed for 2 thru 5 hp drives.

D All controllers which are optionally fitted with a Field

Supply Kit. (These kits may be used only if the dĆc

motor has a wound field.)

(Refer to Paragraph 6.6 for more information.) Whether

or not the controller has a Field Supply may be quickly

determined. (Refer to Figure 4.5.)

Terminal

Block

Diode Bridge

Bracket

Figure 4.5 - Field Supply in Controller

Step 1 Ċ Carefully open the Cover of the controller. (ReĆ

member to lift it directly up 2 inches (50 mm) before hingĆ

ing it around.)
Step 2 Ċ On the Cover, place the POWER ON/OFF cirĆ

cuit breaker in the ON position. (The following steps asĆ

sume that the main aĆc line disconnect is closed.)

DANGER

WITH AĆC POWERAPPLIED AND WITH THE

POWERON/OFF SWITCH IN THE ON POSIĆ

TION, HAZARDOUS VOLTAGE EXISTS IN THE

CONTROLLER. EXERCISE EXTREME CAUTION

WHEN PERFORMING THESE TESTS. PERĆ

SONAL INJURY CAN RESULT.

Step 3 Ċ Use a voltmeter to measure the dĆc voltage

across F1 and F2. (Either slot of the terminal barrier is acĆ

ceptable. This is called out as 3TB on diagrams.) For a

controller with a 115 VAC input, the voltage across F1

and F2 should be approximately 100 VDC For a 230 VAC

input, the voltage should be approximately 200 VDC.
Step 4 Ċ If the proper voltage cannot be read, place the

POWER ON/OFF circuit breaker in the OFF position. DisĆ

connect the aĆc line power. (Do not remove or apply powĆ

er solely with the main disconnect.) Check the Field SupĆ

ply Kit for proper installation. (Refer to Paragraph 6.6 and

to Section 7 Troubleshooting.)