Step 1 Ċ Test the SPEED potentiometer to assure that

it is operating properly. Slowly turn the pot to 10 and obĆ

serve the results at the motor.
Step 2 Ċ If no undesirable operation occurs, move the

SPEED potentiometer to 0 (zero) quickly. Observe if the

deceleration and minimum speed rates are acceptable.
Step 3 Ċ Move the potentiometer to 10 quickly. Observe

if the acceleration and maximum speed rates are acceptĆ

able.
4.3.6 Stopping Ċ The START/STOP rocker switch is

used to stop the drive motor. For safety reasons the

switch is designed to remain in the STOP position after

it is depressed.
For the standard, unmodified control, the drive coasts to

rest after the STOP switch is pushed. With the addition

of the optional Dynamic Braking Kit, pressing the STOP

switch causes a sharp reduction in speed for fast stops.
Assuming the drive is running, press the STOP switch.

Observe the stopping process for proper operation.
4.4 Final Adjustments with LoadĊOnce all the initial

powerĆon adjustments have been performed with acĆ

ceptable results, the final adjustments can be made.

These are done with power on and with the load coupled

to the drive motor. It is important to follow these steps

closely.

DANGER

PROCEDURESOUTLINED IN PARAGRAPHS

4.4.1, 4.4.2, 4.4.3 AND 4.4.5 ARE MADE WITH

AĆC LINE POWER APPLIED TO THE REGENĆ

ERATIVE MINPAK PLUSCONTROLLER AND

THE DRIVE MOTOR. THE MOTOR ISCONĆ

NECTED TO THE LOAD. THESE ADJUSTMENTS

REPRESENT A POTENTIALLY HAZARDOUS

SITUATION AND PERSONAL INJURY COULD

RESULT IF SAFETY PRACTICES ARE NOT OBĆ

SERVED.

4.4.1 Coupling the Load Ċ For final adjustments to be

carried out, it is necessary to put the drive motor under

load.
Step 1 Ċ On the Operator Station, place the POWER

ON/OFF circuit breaker in the OFF position.
Step 2 Ċ Open the main aĆc line disconnect switch. Lock

it open or remove the fuses.
Step 3 Ċ Couple the drive to the load. Make all connecĆ

tions in accordance with instructions shipped with the

units. Assume these will be final, and tighten couplings

accordingly.
Step 4 Ċ Make a final visual inspection of the application

equipment to be sure that no loose equipment has been

left on it. Alert all personnel in the vicinity of the testing to

be carried out.
Step 5 Ċ Reapply all aĆc power and carefully test the

driven equipment. If any malfunction occurs, turn off the

controller immediately and follow troubleshooting proĆ

cedures.

4.4.2 Maximum Speed (Voltage) Ċ The Maximum

Speed potentiometer on the Regulator Module has been

factory preset for 50% of a typical motor base speed of

about 1750 rpm. By means of adjustment, the maximum

speed may be raised to suit the application. The result is

the highest speed that can be set by the operator on the

SPEED dial. The control range is 50Ć100% of rated

speed.
There are two methods for determining if the motor and

driven equipment are operating at an acceptable maxiĆ

mum speed for the application:

D Tachometer
D Visual inspection of machine operation

DANGER

WHEN PERFORMING THISADJUSTMENT PROĆ

CEDURE, DO NOT ALLOW THE DRIVE MOTOR

TO EXCEED ITSRATED MAXIMUM SPEED AS

LISTED ON THE NAMEPLATE. EQUIPMENT

DAMAGE AND SERIOUS PERSONAL INJURY

COULD RESULT.

Step 1 Ċ On the Operator Station, if there is an AUTO/

MANUAL selector switch, put it in the MANUAL position.
Step 2 Ċ Place the RUN/JOG selector switch in the RUN

position.
Step 3 Ċ Place the FORWARD/REVERSE selector

switch in the FORWARD position.
Step 4 Ċ Turn the SPEED dial to a conservative setting

of 2.
Step 5 Ċ Press the START rocker switch.
Step 6 Ċ Open the Cover on the Regenerative MinPak

Plus controller.

DANGER

THE REGENERATIVE MINPAK PLUSCONTROLĆ

LER CIRCUITSARE AT LINE VOLTAGE AT THIS

TIME. USE ALL SAFETY PROCEDURES OUTĆ

LINED HERE. SERIOUS PERSONAL INJURY

COULD RESULT IF SAFETY STEPS ARE NOT

FOLLOWED.

Step 7 Ċ Locate the Maximum Speed potentiometer on

the Regulator Module. (Refer to Figure 4.7.) The letters

MAX SPD are printed on the Module. Note that CW rotaĆ

tion represents an increase in speed. CCW represents a

decrease.
Step 8 Ċ On the Operator Station, increase the SPEED

dial slowly in the direction of 10, which is 100% of full

travel.
If, as the SPEED dial is turned toward the 10 setting, the

speed exceeds the maximum acceptable speed, imĆ

mediately decrease the maximum speed on the SPEED

dial. Use a small insulated slot screwdriver.
NOTE: In some cases. to avoid exceeding the maximum

operating speed. it may be necessary to turn the MaxiĆ

mum Speed potentiometer completely CCW before turnĆ

ing the SPEED dial completely CW.