beautypg.com

Rockwell Automation MinPak Plus DC Drives Kits User Manual

Page 42

background image

41

SYMPTOM

PROBABLE CAUSE

RECOMMENDED PROCEDURES

6. Drive motor

does not

run, but M

contactor

and CR pull

up.

(Use this

procedure

only if conĆ

troller does

not have

optional

Test Meter

Adapter Kit.)

No input signal from

SPEED pot on Control

Station, local or remote.

V If the controller does not have an optional AUTO/MANUAL switch, inspect the

Regulator Module to determine that jumper J4 is inplace. (The jumper is

removed when the AUTO/MANUAL switch is installed.)

V Check the SPEED pot on the Control Station or Faceplate. First place the

POWER ON/OFF circuit breaker in the OFF position. Then open the main aĆc

line disconnect.

V Connect a voltĆohmmeter to the Regulator Module pin connectors Operator

Station inputs. Connect one lead to pin 20 (yellow). Connect the other pin to

28 (green). (Refer to Figure 7.1 for a Local Station and to Figure 3.8 for a

Remote Station.)

V For proper operation, the reading should be 5K ohms.

V Disconnect the VOM lead from pin 28 (green). Connect it to wire 26 (black).

V Turn the SPEED pot from 10 to 0. The resistance should vary from 5K to 10

ohms. If it does not, replace the pot.

FORWARD/REVERSE

switch malfunction.

V Examine Remote Operator Kit on Regulator Module, if used, for firm seating

and proper wiring and pin connections. (Refer to Figure 4.1.)

V Test FORWARD/REVERSE switch. Use basic technique outlined just above

for the START/STOP switch. Here test 67 (purple) against 56 (blue) and 71

(white) against 67 (gray).

7. Drive motor

does not

run, but M

contactor

and CR pull

up.

(Use this

procedure

only if conĆ

troller has

optional

Test Meter

Adapter Kit.)

No input signal from

SPEED pot.

V First check the main power supplies. This must be done with power applied

to the MinPak Plus controller.

V Connect one lead of voltĆohmmeter to test pin 357 on the Test Meter Adapter

Module.

V Connect the second lead to test pin 356 on the Module.

V The reading should be within the range of 10.8 to 11.5 VDC for normal

operation. a Next, remove the lead from pin 356. Place it on pin 456.

V The reading should be within the range of +16 to +28 VDC for normal

operation. a Next, remove the lead from pin 456. Place it on pin 471.

V The reading should be within the range of -16 to -28 VDC for normal

operation.

V If the proper readings are obtained, the power supplies may be assumed to

be operating correctly.

V If incorrect readings are obtained, replace the Regulator Module.

V Next, check the reference voltage input signal. (This changes in direct propĆ

ortion to an increase of SPEED pot voltage caused by a turning of the dial.)

V Connect one lead of a voltĆohmmeter to pin 357 on the Test Meter Adapter

Module.

V Connect the other lead to pin 826. Readings vary from 0 to +8.2 VDC,

depending on the set point of the SPEED pot dial and the position of the

FORWARD/REVERSE switch.

V If no voltage is noted between pins 357 and 826, check to see if jumper J4 on

the Regulator Module is properly placed/removed for the specific controller. (It

is to be in place, as factoryĆshipped, if there is no AUTO/MANUAL switch. It is

to be removed if there is an AUTO/MANUAL switch.)

V If the SPEED pot is functioning normally, and if the J4 jumper is placed/reĆ

moved, as necessary, replace the Regulator Module.

8. Drive motor

does not

run with M

contactor

picked up

and SPEED

pot properly

operating.

(Use this

procedure

only if conĆ

troller does

not have

optional

Test Meter

Adapter Kit.)

No output from Power

Cube.

V Examine armature wiring. First turn POWER ON/OFF circuit breaker to OFF

position. Then open main disconnect switch.

V Check armature wiring for loose connections.

V Turn aĆc power on again.

V Connect a voltĆohmmeter to terminals A1 and A2 on 2TB. (Refer to Figure 3.8.)

V Place the START/STOP switch in the START position.

V Increase the speed reference by turning the SPEED dial in the direction of 10.

V The reading across A1 and A2 should be 0 to 90 VDC for 115 VAC

controllers. It should be 0 to 180 for 230 VAC controllers.

V It no reading is obtained across A1 and A2, it may be necessary to replace

the Power Cube and/or the Regulator Module. In order to determine which,

read on.

DANGER

THE PROCEDURE DESCRIBED HERE IS PERFORMED WITH LIVE AĆC

VOLTAGE APPLIED TO THE CONTROLLER. USE ONLY ONE HAND TO

APPLY VOM LEADS/PROBES. KEEP YOUR OTHER HAND BEHIND YOU

AT ALL TIMES. DO NOT HOLD ONTO THE CONTROLLER FOR SUPĆ

PORT. PERSONAL INJURY MAY RESULT IF THESE PRECAUTIONS ARE

NOT TAKEN.