Alarm and relay status parameters – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual
Page 83

Publication GMSI10-UM025C-EN-P - August 2010
Configuration Parameters 75
Alarm and Relay Status Parameters
Alarm and Relay Status Parameters
Parameter Name
Description
Values/Comments
Alarm Status
States the current status of the alarm.
Possible status values:
• Normal - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is not within the Alert
or Danger Threshold value(s).
• Alert - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is in excess of the
Alert Threshold value(s) but not in
excess of the Danger Threshold
value(s).
• Danger - The alarm is enabled, the
device is in Run mode, there is no
transducer fault, and the current
measurement is in excess of the
Danger Threshold value(s).
• Disarm-The alarm is disabled or the
device is in Program mode.
• Transducer Fault - The alarm is
enabled, the device is in Run mode,
and a transducer fault is detected on
the associated transducer.
• Module Fault - Hardware or
firmware failure, or an error has
been detected and is preventing
proper operation of the device.
Relay Status
States the current status of the relay.
Possible status values: Activated
Not Activated