Identity object (class id 01h), Class attributes, Instance attributes – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual
Page 102: Status, Class attributes instance attributes status, Identity object (class id 01, Instance attributes status
![background image](/manuals/580984/102/background.png)
Publication GMSI10-UM025C-EN-P - August 2010
94 DeviceNet Objects
Identity Object
(Class ID 01
H
)
The Identity Object provides identification and general information about the
device.
Class Attributes
The Identity Object provides no class attributes.
Instance Attributes
Status
The Status is a 16 bit value. The following bits are implemented.
Table C.1 Identity Object Instance Attributes
Attr ID
Access
Rule
Name
Data Type
Default Value
1
Get
Vendor ID
UINT
668 = Entek
2
Get
Device Type
UINT
109 (Specialty I/O)
3
Get
Product Code
UINT
39 (0x27) XM-160
40 (0x28) XM-161
41 (0x29) XM-162
4
Get Revision:
Major
Minor
STRUCT OF
USINT
USINT
Value varies with each firmware revision.
Value varies with each firmware revision.
5
Get
Status
WORD
6
Get
Serial Number
UDINT
7
Get Product
Name
SHORT_
STRING
"XM-160 Overall Vibration Module"
"XM-161 Overall Vibration Module"
"XM-162 Overall Vibration Module"
Table C.2 Identity Object Status
Bit
Name
Description
0
Owned
TRUE indicates that the module has an owner. More
specifically, the Predefined Master/Slave Connection Set
has been allocated to a master.
1
Reserved, set to 0
2
Configured
This bit is set whenever a saved configuration is
successfully loaded from non-volatile memory. This bit is
cleared whenever the default configuration is restored or
loaded.