Mounting the module – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual
Page 61
Publication GMSI10-UM025C-EN-P - August 2010
Installing the XM-160/161/162 Direct Vibration Module 53
Mounting the Module
The Direct Vibration modules mount on the XM-947 terminal base unit, Cat.
No. 1440-TB-H. You should mount the module after you have connected the
wiring on the terminal base unit.
1. Make certain the keyswitch (A) on the terminal base unit (C) is at
position 7 as required for the XM-160, XM-161 and XM-162 modules.
ATTENTION
The Direct Vibration modules are compatible only with the
XM-947 terminal base unit. The keyswitch on the terminal
base unit should be at position 7 for the modules.
Do not attempt to install the XM-160, XM-161, and
XM-162 modules on other terminal base units.
Do not change the position of the keyswitch after
wiring the terminal base.
ATTENTION
This module is designed so you can remove and insert it
under power. However, when you remove or insert the
module with power applied, I/O attached to the module
can change states due to its input/output signal changing
conditions. Take special care when using this feature.
WARNING
When you insert or remove the module while power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
IMPORTANT
Install the overlay slide label to protect serial connector and
electronics when the serial port is not in use.