Instances, Instance attributes, Services – Rockwell Automation 1440-VDRP06-00RH XM-160/161/162 Direct Vibration Module User Manual
Page 131: Instances instance attributes services, Instance attributes services
Publication GMSI10-UM025C-EN-P - August 2010
DeviceNet Objects 123
Instances
There are 6 instances of this object.
Instance Attributes
Services
1
Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object
for more information.
Table C.40 4-20mA Output Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
3
Get
Value
REAL
The current output value.
mA
4
Get/Set
Enable
BOOL
Indicates whether this
4-20mA output is
enabled.
0 = Disabled
1 = Enabled
5
Get/Set
Max Range
REAL
The measured value
associated with 20mA.
6
Get/Set
Min Range
REAL
The measured value
associated with 4mA.
Table C.41 4-20mA Output Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
1