68 Configuration Parameters
Sets the relay activation logic.
• A or B - Relay is activated when either Alarm A or
Alarm B meets or exceeds the selected Alarm
Status condition(s).
• A and B - Relay is activated when both Alarm A
and Alarm B meet or exceed the selected Alarm
Status condition(s).
• A Only - Relay is activated when Alarm A meets
or exceeds the selected Alarm Status
condition(s).
Options: A only
A or B
A and B
Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select an alarm only in Alarm A.
Options: Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Note: You can only select an alarm
that is enabled.
Sets the alarm conditions that will cause the relay to
activate. You can select more than one.
• Normal - The current measurement is not within
excess of any alarm thresholds.
• Alert - The current measurement is in excess of
the alert level threshold(s) but not in excess of the
danger level threshold(s).
• Danger - The current measurement is in excess of
the danger level threshold(s).
• Disarm-The alarm is disabled or the device is in
Program mode.
• Xdcr Fault - A transducer fault is detected on the
associated transducer.
• Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing
proper operation of the device.
Options: Normal
Danger
Xdcr Fault
Alert
Disarm
Module Fault
Check to enable.
Clear to disable.
Relay Installed
Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.
If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.
Relay Parameters
Parameter Name
Description
Options/Comments
XM Configuration
Utility
EDS File
Activation Logic
Logic
XM Configuration
Utility
EDS File
Alarm A/B
Alarm
Identifier
A/B
XM Configuration
Utility
EDS File
Alarm Status to
Activate On
Alarm Levels
XM Configuration
Utility
EDS File
Check = Physical
Relay
Installed =
Physical Relay
Clear = Virtual Relay Not Installed =
Virtual Relay