Test the TP Predefined Function
The TP instruction starts an internal timer when input IN makes a transition
from low to high, and energizes the output at the same time. When the elapsed
time ET increments up to the given value PT, it de-energizes the output. To test
the operation, we connect a push button to I03, and a pilot light to output O02.
1. Press the ESC button to return to the Main Menu.
2. Press the UP arrow button to select Mode Switch. Press the OK button.
3. Press the DOWN arrow button to select RUN mode. Press the OK
button.
4. Press the OK button to confirm the RUN mode selection.
5. The screen indicates that the controller is in RUN mode. Press the ESC
button to return to the Main Menu.
6. Press the DOWN arrow button to select SR FUNCTION. Press the OK
button.
7. Press the UP arrow button twice to select Output 2.