beautypg.com

Compatibility, Work with a locked controller, Compatibility work with a locked controller – Rockwell Automation 2080-LC10-12DWD Micro810 Programmable Controllers User Manual User Manual

Page 48

background image

38

Rockwell Automation Publication 2080-UM001D-EN-E - September 2012

Chapter 7 Controller Security

The controller password is also backed up to the memory backup module (that is,
2080-MEMBAK-RTC for Micro830 and Micro850 and 2080-LCD for
Micro810 controllers). If the password in the backup module is different from the
memory backup module, then restore operation will fail.

Compatibility

The Controller Password feature is supported on:

• Connected Components Workbench revision 2 and later
• Micro800 controllers with revision 2 firmware

For users with earlier versions of the software and/or hardware, refer to the
compatibility scenarios below.

Connected Components Workbench revision 1 with Micro800 controller
firmware revision 2

Connection to a Micro800 controller with firmware revision 2 using an earlier
version of the Connected Components Workbench software (revision 1) is
possible and connections will be successful. However, the software will not be
able to determine whether the controller is locked or not.

If the controller is not locked, access to the user application will be allowed,
provided the controller is not busy with another session. If the controller is
locked, access to the user application will fail. Users will need to upgrade to
revision 2 of the Connected Components Workbench software.

Connected Components Workbench revision 2 with Micro800 controller
firmware revision 1

Connected Components Workbench revision 2 is capable of "discovering" and
connecting to Micro800 controllers with firmware revision earlier than revision 2
(that is, not supporting the Controller Password feature). However, the
Controller Password feature will not be available to these controllers. The user
will not be able see interfaces associated with the Controller Password feature in
the Connected Components Workbench session.

Users are advised to upgrade the firmware. See

Flash Upgrade Your Micro800

Firmware on page 267

for instructions.

Work with a Locked
Controller

The following workflows are supported on compatible Micro800 controllers
(firmware revision 2) and Connected Components Workbench software
revision 2.

TIP

For instructions on how to set, change, and clear controller passwords,
see

Configure Controller Password on page 279

.