Rockwell Automation Publication 2080-UM001D-EN-E - September 2012

29

Troubleshooting Chapter 5

0xF8A1

The DOY parameters are invalid.

Perform the following:

Correct the program to ensure that there are no invalid parameters.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller on Run mode.

0xF8A2

The HSC parameters are invalid.

Perform the following:

Correct the program to ensure that there are no invalid parameters.

Build and download the program using Connected Components Workbench.

Put the Micro800 controller on Run mode.

0xFFzz
(zz indicates the
last byte of the
program number.
Only program
numbers up to
0xFF can be
displayed. For
program numbers
01x00 to 0xFFFF,
only the last byte
is displayed.)

A user-created fault from Connected
Components Workbench has occurred.

Contact your local Rockwell Automation technical support representative if the error
persists.

List of Error Codes for Micro800 controllers

Error Code

Description

Recommended Action