8. Press the push button connected to I03. If the value of RTC is in the range
of Day-Time setting for CHANNEL A, the pilot light turns on.
Configure Countdown (CTD)
1. Power up the Micro810 controller.
The Micro810 splash screen briefly appears after power up.
2. The status display shows the PROG status, the day and time, and the I/O
status. Press the ESC and OK buttons at the same time to navigate to the
Main Menu.
3. Press the DOWN arrow button once to select SR Function. Press the OK
button. The function block for controlling Output 0 is displayed.
4. Press the RIGHT arrow button once to select the TON instruction
parameter field.
5. Press the UP arrow button three times to change to CTD instruction.
CTD – Sample Parameter Configuration
Parameter field
Configuration value
Q
Q00
CLK
I01
LOAD
I02
PV
00010