beautypg.com

Rockwell Automation 2080-LC10-12DWD Micro810 Programmable Controllers User Manual User Manual

Page 26

background image

18

Rockwell Automation Publication 2080-UM001D-EN-E - September 2012

Chapter 4 Wire Your Controller

of surge suppression to protect and extend the operating life of the controllers
output contacts is required. Switching inductive loads without surge suppression
can

significantly reduce the life expectancy of relay contacts. By adding a

suppression device directly across the coil of an inductive device, you prolong the
life of the output or relay contacts. You also reduce the effects of voltage
transients and electrical noise from radiating into adjacent systems.

The following diagram shows a typical PLC's output with a suppression device.
We recommend that you locate the suppression device as close as possible to the
load device.

If the outputs are DC, we recommend that you use an 1N4004 diode for surge
suppression, as shown below. For inductive DC load devices, a diode is suitable. A
1N4004 diode is acceptable for most applications. A surge suppressor can also be
used. See

page 19

for recommended suppressors. As shown below with a typical

PLC's output, these surge suppression circuits connect directly across the load
device.

Suitable surge suppression methods for inductive AC load devices include a
varistor, an RC network, or an Allen-Bradley surge suppressor, all shown below.
These components must be appropriately rated to suppress the switching

+DC or L1

Suppression
Device

DC COM or L2

AC or DC
Outputs

Load

VAC/DC
Out 0

Out 1
Out 2

Out 3

Out 4
Out 5
Out 6

Out 7

COM

+24V DC

IN4004 Diode

Relay or Solid
State DC Outputs

24V DC common

VAC/DC

Out 0
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
Out 7
COM

(A surge suppressor
can also be used.)