Rockwell Automation 2080-LC10-12DWD Micro810 Programmable Controllers User Manual User Manual
Page 56
48
Rockwell Automation Publication 2080-UM001D-EN-E - September 2012
Appendix A Specifications
Micro810 High Current Relay Chart
Relay Output Life
Attribute
Value
Mechanical
10,000,000 cycles
Electrical with rated load
50,000 cycles
Embedded RTC
Attribute
Value
Resolution READ_RTC()
1 sec
Accuracy
± 12 sec/month @ 25 °C
± 160 sec/month @ 0…55 °C
Power off
Supercap — 5 days @ 40 °C or lower
Supercap life — 5 years @ 40 °C, 14.5 years @ 25 °C
Maximum
Volts
IEC 947
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
AC-15
30 A
3 A
8 A
3600V A
360V A
240V AC
AC-15
15.0 A
1.5 A
8 A
3600V A
360V A
125V DC
DC-13
0.22 A
1.0 A
28V A
250V DC
DC-13
0.11 A
1.0 A
28V A
24V DC
DC-13
1.2 A
5.0 A
28V A
This manual is related to the following products: