Chapter 2 About Your Controller

• Install emergency-stop switches and the master control relay in your

system. Make certain that relay contacts have a sufficient rating for your
application. Emergency-stop switches must be easy to reach.

• In the following illustration, input and output circuits are shown with

MCR protection. However, in most applications, only output circuits
require MCR protection.

The following illustrations show the Master Control Relay wired in a grounded
system.

TIP

In most applications input circuits do not require MCR protection;
however, if you need to remove power from all field devices, you must
include MCR contacts in series with input power wiring.