beautypg.com

Configure doy – Rockwell Automation 2080-LC10-12DWD Micro810 Programmable Controllers User Manual User Manual

Page 83

background image

Rockwell Automation Publication 2080-UM001D-EN-E - September 2012

75

Quickstarts Appendix C

6. Press the DOWN arrow button once and select SR FUNCTION. Press

the OK button. The TON function block to control Output 0 becomes
available.

7. Press the push button connected to I01. ET starts to elapse.

8. When the current ET equals PT, output O00 is energized, and the pilot

light turns on.

Configure DOY

1. Power up the Micro810 controller.

The Micro810 splash screen briefly appears after power up.

2. The status display shows PROG mode, the day and time, and the I/O

status. Press the ESC and OK buttons at the same time to navigate to the
Main Menu.

3. Press the DOWN arrow button once to select SR function. Press the OK

button.

4. Press the DOWN arrow button once to navigate to the function block

controlling Output 3 (DOY).

DOY – Sample Parameter Configuration

Parameter Field

Configuration Value

Q

Q03

Channel

A

EN

I03

Y/C

0

On

11/08/18 (YY/MM/DD)

Off

11/08/19 (YY/MM/DD)