Rockwell Automation 1756-HSC ControlLogix High Speed Counter Module User Manual

Page 67

background image

Rockwell Automation Publication 1756-UM007C-EN-P - November 2011

Configure the 1756-HSC Module

67

Storage Mode

Choose how the pulse count will be
stored (with the mode selected in the
above field) if required for an
accumulated count. These are the
values:

• No Store Mode (default)

• Store and Continue Mode

• Store, Wait, and Resume Mode

• Store and Reset, Wait, and Start

Mode

• Store and Reset, and Start Mode
See

Storage Modes in Chapter 2

for

details.

Rollover

Defaults to zero (0), which is the
equivalent to a full count range
(16,777,214). When the accumulated
count value in the Present Value tag
reaches the rollover value, it resets to
zero (0) and begins counting again.

Range is 0…16,777,214.

This configuration setting can be
overridden by a value in the Output tag
for the HSC Data-extended format only.
See

Rollover in Chapter 2

for details.

Preset

Box defaults to zero (0) if a Preset
command is issued. The 1756-HSC
module’s Present Value tag will be set to
the present value.

Range is 0…Rollover value.

This configuration setting can be
overridden by a value in the Output tag
for the HSC Data-extended format only.
See

Preset in Chapter 2

for details.

Scaler

Defaults to zero (0).

For Frequency mode, the Scaler
determines the amount of time in
milliseconds the 1756-HSC module
counts incoming pulses. Range 0…2000
ms in 10 ms increments. A value of zero
(0) is equivalent to 1000 ms.

For Period Rate/Continuous Rate modes,
pulses will be used to count internal
4 MHz pulses. Allowable values are
0, 1, 2, 4, 8, 16, 32, 64, 128, 256.

A value of zero is equivalent to 1. Valid
with the HSC Data-extended
Comm Format only.

Field

Description