Configure the 1756-HSC Module

61

7. From the Comm Format pull-down menu, choose a communication

format.

See

page 62

for a description of the formats and the associated tags that

are created during the download.

8. In the Revision box, make sure to match the actual revision for your

module.

This setting works in conjunction with the electronic keying to
determine the connection.

9. Choose an electronic keying method.

See

page 73

for details.

10. Do one of the following to either accept default configuration settings

or edit configuration data.
a. To accept the default configuration settings, make sure

Open Module Properties is not checked and then click OK.

b. To set up a custom configuration, make sure Open Module

Properties is checked and then click OK.

The New Module Properties dialog box appears with tabs for entry

of additional configuration settings.

IMPORTANT

Make sure you select the correct communication format for
your application because you cannot change the selection
after the program is downloaded with the controller. You
will have to reconfigure the module to change the
communication format.

IMPORTANT

Controllers that have RSLogix 5000 software,
version 17 or earlier, should use Compatible Keying for
the 1756-HSC/B module. You must upgrade to
version 18 or later if Exact Match is required; otherwise,
there will be no connection with the controller.