Rockwell Automation 1756-HSC ControlLogix High Speed Counter Module User Manual
Page 61

Rockwell Automation Publication 1756-UM007C-EN-P - November 2011
Configure the 1756-HSC Module
61
7. From the Comm Format pull-down menu, choose a communication
format.
See
for a description of the formats and the associated tags that
are created during the download.
8. In the Revision box, make sure to match the actual revision for your
module.
This setting works in conjunction with the electronic keying to
determine the connection.
9. Choose an electronic keying method.
See
for details.
10. Do one of the following to either accept default configuration settings
or edit configuration data.
a. To accept the default configuration settings, make sure
Open Module Properties is not checked and then click OK.
b. To set up a custom configuration, make sure Open Module
Properties is checked and then click OK.
The New Module Properties dialog box appears with tabs for entry
of additional configuration settings.
IMPORTANT
Make sure you select the correct communication format for
your application because you cannot change the selection
after the program is downloaded with the controller. You
will have to reconfigure the module to change the
communication format.
IMPORTANT
Controllers that have RSLogix 5000 software,
version 17 or earlier, should use Compatible Keying for
the 1756-HSC/B module. You must upgrade to
version 18 or later if Exact Match is required; otherwise,
there will be no connection with the controller.