Counter mode – Rockwell Automation 1756-HSC ControlLogix High Speed Counter Module User Manual

Page 19

background image

Rockwell Automation Publication 1756-UM007C-EN-P - November 2011

Counter Modes

19

Counter Mode

This is the 1756-HSC module’s default operational mode that counts incoming
pulses using input A. You can control the starting and ending points of the
accumulated count depending on how you have configured the module.

In the Counter mode, the count increases or decreases based on the state of
input B, which can be a random signal. If input B is high, the counter will
count down. If input B is low or floating (that is, not connected to a voltage
source), the counter counts up. Counting is done on the leading-edge of
input A.

Input Z is used in Counter mode only if a Store Count mode is enabled.
See

page 23

for details on the Storage modes.

Counter Mode

Input B

Direction of Counter

High

Down

Low or floating (not connected)

Up

Single-phase Pulse Generator

Count Up

Count Down

1756-HSC Module

Increment/Decrement Count

Input A

Input B

Input A

Input B

+

...

1

2

3

0

1

2

41688

Accumulated Count
in Present Value Tag

Positive Frequency

Negative Frequency

Directional Frequency
in Totalizer Tag

Input Z (optional)

Pulse Count

...