beautypg.com

Rockwell Automation 1756-HSC ControlLogix High Speed Counter Module User Manual

Page 48

background image

Rockwell Automation Publication 1756-UM007C-EN-P - November 2011

48 Install and Wire the ControlLogix High-speed Counter Module

Wire an Allen-Bradley Bulletin 872 3-Wire DC Proximity Sensor

Use the table and diagram to connect the 1756-HSC module to an
Allen-Bradley 872 three-wire DC proximity sensor.

Application

A0 Connections

B0 Connections

Z0 Connections

PNP (Sourcing)
N.O.

Black - A0 12…24V DC
Blue, PS(-)-A0
Return

Jumper B0 12…24V DC
to B0 Return

Jumper Z0 12…24V DC
to Z0 Return

Jumpers

Black

Blue

Z1 (12…24V)

Z1 (5V)

Z1 (RET)

B1 (12…24V)

B1 (5V)

B1 (RET)
A1 (12…24V)
A1 (5V)

A1 (RET)
Not Used

Not Used

Not Used

Z0 (12…24V)

Z0 (5V)

Z0 (RET)

B0 (12…24V)

B0 (5V)

B0 (RET)
A0 (12…24V)
A0 (5V)

A0 (RET)
Not Used

Not Used

Not Used

COMMON 0
COMMON 0

COMMON 0

DC-0(+)

Out 2

Out 3

COMMON 1

COMMON 1
COMMON 1

DC-1(+)

Out 0

Out 1

12…24V DC

12…24V DC
Return

41602

Allen-Bradley
Bulletin 872
3-Wire DC
Proximity
Sensor

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

1

3

5

7

9

11

13

15

17

19

21

23

25

27

29

31

33

35