Counter Modes

21

Encoder x4

Encoder x4 mode is identical to x1, except this mode counts on the leading
and trailing edges of A and B to provide a greater number of pulse counts. The
greater the number of pulse counts the better the module can
determine position.

Input Z is used in Encoder mode only if a Store Count mode is enabled.
See

page 23

for details on the storage modes.

Encoder x4 Mode

Maximum frequency in Encoder x1 and x4 modes = 250 kHz (assuming
50% duty cycle), with a minimum pulse width at this frequency of 2 s. The
module assumes a 90° phase (A/B°) difference between channels.

Input A

Quadrature Encoder

1756-HSC Module

Input B

Input A

Input B

Input A

Input B

B Leads A 90°

A Leads B 90°

1

2

3 4

5 6 7

8

9 10 11 12

1

2

3

4

5

6

7

8

9

10

11

0

41689

Accumulated Count
in Present Value Tag

Directional Frequency
in Totalizer Tag

Positive Frequency

Negative Frequency

Input Z (optional)