Parameter and variable descriptions 6-39 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual
Page 95

PARAMETER AND VARIABLE DESCRIPTIONS
6-39
1557-UM050F-EN-P – June 2013
Logic Status 1 [Logic status 1]
Linear number:
258
Minimum value:
0000 Hex
Maximum Value:
FFFF Hex
Analog Output Scaling: NA
This variable is the value of logic status 1, the status word that has the same definition for all drives. It is bit
encoded as shown below:
xxx1H - enabled
xxx2H - running
xxx4H - forward command
xxx8H - forward rotation
xx1xH - accelerating
xx2xH - decelerating
xx4xH - warning
xx8xH - fault
x1xxH - at speed command
x0xxH - port 0 local
x2xxH - port 1 local
x4xxH - port 2 local
x6xxH - port 3 local
x8xxH - port 4 local
xAxxH - port 5 local
xCxxH - port 6 local
xExxH - no local
0xxxH - external speed command 0 selected (analog input 1L)
1xxxH - preset speed command 1 selected
2xxxH - preset speed command 2 selected
3xxxH - preset speed command 3 selected
4xxxH - preset speed command 3 selected
5xxxH - preset speed command 3 selected
6xxxH - preset speed command 3 selected
7xxxH - preset speed command 3 selected
8xxxH - external speed command 8 selected (analog input 1M)
9xxxH - port 1 speed command selected
AxxxH - port 2 speed command selected
BxxxH - port 3 speed command selected
CxxxH - port 4 speed command selected
DxxxH - port 5 speed command selected
ExxxH - port 6 speed command selected
FxxxH - preset jog speed command selected