Parameter and variable descriptions 6-13 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual
Page 69

PARAMETER AND VARIABLE DESCRIPTIONS
6-13
1557-UM050F-EN-P – June 2013
Speed Feedback Mode [Speed fdbk mode]
Linear number:
89
Minimum value:
0
Maximum value:
1
Default value:
0
This parameter specifies the type of speed feedback used.
0
stator frequency with slip compensation
1
tachometer/encoder
The drive automatically switches to stator frequency feedback when a tach loss fault occurs. If the tach loss
fault is successfully cleared the drive switches back to tach feedback mode.
Torque Control Mode [Trq control mode]
Linear number:
90
Minimum value:
0
Maximum value:
5
Default value:
1
This parameter specifies the torque control mode.
0
zero torque
1
speed regulator
2
external torque command
3
speed regulator with external positive torque limit
4
speed regulator with external negative torque limit
5
sum of speed regulator and external torque command
Torque Command External [Trq command ext]
Linear number:
91
Minimum value:
-1.500
Maximum value:
1.500
Default value:
0.000
The function of this parameter depends on the torque control mode:
0
not used
1
not used
2
torque command
3
positive torque limit
4
negative torque limit
5
torque command
A value of 1.00 corresponds to rated motor torque. Note that motoring torque is positive for forward rotation
and negative for reverse rotation.
Prior to Rev 4.60/5.00, this parameter was scaled in per unit based on the motor rated kVA and was about 10%
lower.