COMMISSIONING
9-1
1557-UM050F-EN-P – June 2013
Introduction
This chapter will assist the user in start-up of a Bulletin 1557 drive. This chapter contains reference material
with information regarding:
Recommended tools
Pre-Power checks
Verification of proper control voltages
Gating checks
Tuning (Autotuning as well as manual tuning)
WARNING: Servicing energized industrial control equipment can be hazardous.
Severe injury or death can result from electrical shock, burn, or unintended
actuation of control equipment. Hazardous voltages may exist in the cabinet
even with the circuit breaker in the off position. Recommended practice is to
disconnect or lock out control equipment from power sources, and confirm
discharge of stored energy in capacitors. If it is necessary to work in the vicinity
of energized equipment, the safety related work practices of NFTA 70E,
Electrical Safety requirements for Employee Work places, must be followed.
CAUTION: The CMOS devices used on the control circuit boards can be
destroyed or damaged by static charges. If personnel will be working near static
sensitive devices, they must be appropriately grounded.
Recommended Tools and Equipment
The following list of tools is highly recommended for startup and tuning of a 1557 Medium Voltage Drive.
Oscilloscope with memory
Multimeter with assorted clip leads
Assorted hand tools, with standard inch sockets and wrenches
Approved contact type hot stick with appropriate high voltage gloves
Static strap
5 kV Megger
PLCC Chip Puller (Extraction tool)
Torque Wrench