34 troubleshooting – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual
Page 276

10-34
TROUBLESHOOTING
1557-UM050F-EN-P – June 2013
Drive Faults
Fault
Code #
FAULT
MESSAGE
F
Description
F0
Line selftst
F
The line converter control board has failed its power up self-test. This
fault can only be cleared by turning off the control power.
F1
Line param
F
The parameters stored in EEPROM on the Line Converter control
board have been corrupted.
F2
Line s/w w/d
F
Line side software watchdog has expired.
F3
Line h/w w/d
F
Line side hardware watchdog timer has expired
F4
Line s/w o/c
F
The line current feedback has exceeded the level in P161 for the
duration in P162.
F5
Line h/w o/c
F
The instantaneous line current has exceeded the level in P169 for the
duration in P170.
F6
Line ac o/v
F
The line voltage has exceeded the level in P165 for the duration in
P166
F7
Line dc o/v
F
The line side dc link voltage has exceeded the level in P187 for the
duration in P188.
F8
12p phasing
or
Line phasing
F
This fault indicated on 12 or 18 pulse drives only. Either the phase
rotation of the line voltage is reversed or the phase angle relationships
between the slave bridge(s) and the master bridge is incorrect.
Firmware revision numbers less than 5.00 termed “12 p phasing”
Firmware revision numbers grea
ter than 5.00 termed “Line phasing”
F9
Ground fault
F
The signal from the ground fault CT has exceeded the level in P171
for the duration in P172.
F10
Line thy open
F
An open thyristor has been detected in the line converter.
F11
Line thy short
F
A shorted thyristor has been detected in the line converter.
F12
Ac cntrl pwr
F
The 48Vdc-power supply has reported an AC voltage fault. Check
control power supply.
F13
Ln unbalance
F
The unbalance in the line voltage or current feedback is greater than
0.1 pu for more than 100 cycles. If the drive is running it is a current
balance fault, and if the drive is not running it is a voltage balance fault.
F14
Input open
F
The input contactor has opened when the drive was running.
F15
Pulse number
F
Parameter Pulse Number (P153) has been changed and the drive
control power was not cycled.
F16
Mtr selftst
F
The machine converter control board has failed its power up self-test.
This fault can be cleared only by turning off the control power.
F17
Mtr parm
F
The parameters stored in EEPROM on the Machine Converter
Control Board have been corrupted.
F18
Mtr s/w w/d
F
Motor side software watchdog timer has expired.
F19
Mtr h/w w/d
F
Motor side hardware watchdog timer has expired.
F20
Mtr s/w o/c
F
The motor current has exceeded the level in P177 for the duration in
P178.
F21
Mtr h/w o/c
F
The motor current has exceeded the level in P177 for the duration in
P178.
F22
Mtr ac o/v
F
The motor voltage has exceeded the level in P181 for the duration in
P182.
F23
Mtr dc o/v
F
The motor side DC link voltage has exceeded P187 for the duration in
P188.