beautypg.com

Specifications chapter 3 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 9

background image

SPECIFICATIONS

CHAPTER 3


1557-UM050F-EN-P – June 2013


The electrical and environmental specifications of the Bulletin 1557 MV Drive are provided below:


Input Voltages:

2300Vac ± 10%, 3-Phase

3300Vac ± 10%, 3-Phase

4160Vac ± 10%, 3-Phase

6900Vac ± 10%, 3-Phase



Input Frequency:

50/60Hz ± 3Hz



Efficiency:

97% at full load (minimum)



Output Voltage:

0 to 2300Vac, 3-Phase

0 to 3300Vac, 3-Phase

0 to 4160Vac, 3-Phase

0 to 6900Vac, 3-Phase



Output Frequency:

6Hz to 75Hz (Without Tach)

0.2Hz to 75 Hz (With Tach)


Speed Regulation:

0.5% of maximum speed (Without Tach)

0.1% of maximum speed (With Tach)


Speed Reference:

0 to 10V dc or

4 to 20 mA dc



Operating Temperature:

Ambient temperature must be within the range of 0° to 40°C
with a relative humidity of up to 95% (non-condensing)



Storage Temperature:

Ambient temperature must be within the range of

–40° to 70°C



Altitude:

No derating below 1000 m above sea level