Parameter and variable descriptions 6-57 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual
Page 113
PARAMETER AND VARIABLE DESCRIPTIONS
6-57
1557-UM050F-EN-P – June 2013
Parameters and Variables Listed by Group
Categories:
1 - rating or configuration parameter set at the factory
2 - application parameter set at the factory or at commissioning
3 - tuning parameter set at commissioning
S - synchronous drive parameter not used for induction motors
All other parameters are normally left at the default setting.
1
Feature Select
Name
Minimum
Maximum
Default
Units
Cat.
1
Contactor Configuration
0
7
0
2
3
Automatic Restart Delay
0.000
10.000
0.000
sec
2
4
Test Mode
0
4
0
6
Speed Command Select 0
1
15
1
2
7
Speed Command Select
0
15
NA
8
Reverse Enable
0
1
0
2
9
Speed Command Select 8
1
15
9
2
10
Contactor Open Delay
0.0
57.0
0.0
min
2
13
Parameter Level
0
3
2
15
Drive Control FRN
0.00
99.99
NA
16
Communications Proc FRN
0.00
99.99
NA
2
Nameplate Parameters
Name
Minimum
Maximum
Default
Units
Cat.
17
Rated Line Frequency
50
60
60
Hz
1
20
Capacitor kvar
1
7500
100
kvar
1
21
Capacitor Volts
1000
10000
2400
V
1
22
Rated Motor Volts
1000
7200
2300
V
1
23
Rated Motor Amps
10
1000 or 1400
60
A
1
24
Rated Motor kw
30
7500 or 10000 187
kw
1
25
Rated Motor hp
40
10000 / 13400 250
hp
1
26
Rated Motor rpm
150.0
3600.0
1185.0
rpm
1
27
Link Inductance
1.0
600.0
64.0
mh
1
28
Capacitor Frequency
50
60
60
Hz
1
29
Rated Motor Frequency
40
90
60
Hz
1
30
Motor Type
0
1
0
1
31
Service Factor
0.75
1.25
1.00
1
32
Drive Type
0
1
0
1
3
Speed Command Parameters
Name
Minimum
Maximum
Default
Units
Cat.
33
Preset Speed Command 1
0.5
90.0
30.0
Hz
34
Preset Speed Command 2
0.5
90.0
35.0
Hz
35
Preset Speed Command 3
0.5
90.0
40.0
Hz
40
Preset Jog Speed
1.0
60.0
6.0
Hz
41
Speed Command 0 Minimum
-127.0
127.0
6.0
Hz
2
42
Speed Command 0 Maximum
0.0
127.0
60.0
Hz
2
43
Speed Command 8 Minimum
-127.0
127.0
6.0
Hz
2
44
Speed Command 8 Maximum
0.0
127.0
60.0
Hz
2
45
Speed Command 9 Minimum
0.0
127.0
6.0
Hz
2
46
Speed Command 9 Maximum
0.0
127.0
60.0
Hz
2
47
Speed Command Minimum
1.0
75.0
6.0
Hz
2
48
Speed Command Maximum
1.0
75.0
60.0
Hz
2