Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 99
![background image](/manuals/578785/99/background.png)
Enhanced DeviceNet Adapter’s Parameters
B-11
9
Idle Flt Action
Fault
Zero Data
Hold Last
Fault Cfg
Fault
Yes
No
Determines the action the adapter should
instruct the SCANport product to take if the
adapter detects that the PLC is set to program
mode.
Important: If you change this parameter’s
value, the user application may not be able to
control the product after a fault.
10
Comm Flt Action
Fault
Zero Data
Hold Last
Fault Cfg
Fault
Yes
No
Determines the action the adapter should
instruct the SCANport product to take if the
adapter detects a network failure.
Important: If you change this parameter’s
value, the user application may not be able to
control the product after a fault.
11
Fault Cfg Logic
0 – 65535
0
Yes
No
Provides the logic command data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
12
Fault Cfg Ref
0 – 65535
0
Yes
No
Provides the analog reference data to the
SCANport product when the adapter is
instructed to use the values for the Fault Cfg
parameters.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power Cycle
Description
Important: For information on accessing and editing parameters, refer to Chapter 3, Configuring the 1203-GU6 Using a Serial
Connection, or Chapter 4, Configuring the 1203-GU6 or 1336-GM6 Adapter Using RSNetWorx for DeviceNet.
!
ATTENTION: Risk of severe bodily
injury or equipment damage exists.
The
Idle Flt Action
(9) parameter
allows the user to change the default
configuration that would allow the
module and associated drive to
continue to operate if communication
is lost. Precautions should be taken
to assure that your settings for these
parameters and your application do
not create a hazard of bodily injury or
equipment damage.
!
ATTENTION: Risk of severe bodily
injury or equipment damage exists. The
Comm Flt Action
(10) parameter allows
the user to change the default
configuration that would allow the
module and associated drive to
continue to operate if communication is
lost. Precautions should be taken to
assure that your settings for these
parameters and your application do not
create a hazard of bodily injury or
equipment damage.