C-19, Class attributes instance attributes – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 127
DeviceNet Objects
C-19
Class Code 0x97 — SCANport
Pass-Through Fault Object
The SCANport Pass-Through Fault Object provides information on
the product’s fault queue.
Class Attributes
Instance Attributes
Attribute ID
Access Rule
Name
Data Type
Description
0
Set
Write Fault Command
BYTE
1 = Clear Faults
2 = Clear Fault Queue
3 = Reset Product
1
Get
Read Number of Fault
Queue Entries
BYTE
Reads the number of fault queue entries.
2
Get
Read Fault Queue Trip
Index
BYTE
Reads the index of the fault that tripped the product.
Attribute ID
Access Rule
Name
Data Type
Description
0
Get
Read Fault Queue Entry
Full/All Info
STRUCT of
Fault Text
ARRAY of BYTE
16 character string (no length information, no
terminating null).
Fault Code
WORD
Fault Code.
Fault Time Stamp
STRUCT
BYTE
1/100 Second (0 – 99).
BYTE
Second (0 – 59).
BYTE
Minute (0 – 59).
BYTE
Hour (0 – 23).
BYTE
Day of Week (0 – 6).
➀
BYTE
Date (1 – 31).
BYTE
Month (1 – 12).
BYTE
Year (0 – 99
➁
).
128
Get
Fault Code and Time
Stamp
STRUCT of
Fault Code
WORD
Fault Code.
Fault Time Stamp
STRUCT of
BYTE
1/100 Second (0 – 99).
BYTE
Second (0 – 59).
BYTE
Minute (0 – 59).
BYTE
Hour (0 – 23).
BYTE
Day of Week (0 – 6).
➀
BYTE
Date (1 – 31).
BYTE
Month (1 – 12).
BYTE
Year (0 – 99
➁
).
129
Get
Read Fault Text String
Only
ARRAY of BYTE
16 character string (no length information, no
terminating null).