Supported pccc messages, Related documentation – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 136
D-2
Supported PCCC Messages
Supported PCCC Messages
The 1203-GU6 and 1336-GM6 support the following PCCC
messages:
Related Documentation
For more information on PCCC messages, refer to the DF1 Protocol
and Command Set Reference Manual, publication 1770-6.5.16.
CMD
FNC
Message Definition
Supported?
0x06
0x03,4,5,0,1
Identify Host and Some Status
Yes
0x0F
0x67
PLC-5 Typed Write
Yes
0x0F
0x68
PLC-5 Typed Read
Yes
Logical ASCII Address
Yes
Logical Binary Address
No
PLC-2 System Address
No
PLC-3 Symbolic Address
No
0x0F
0xA1
SLC-500 Protected Typed Logical Read w/ 2 Address Fields — File, Element
No
0x0F
0xA2
SLC-500 Protected Typed Logical Read w/ 3 Address Fields — File, Element,
Sub-Element
Yes
0x0F
0xA9
SLC-500 Protected Typed Logical Write w/ 2 Address Fields — File, Element
No
0x0F
0xAA
SLC-500 Protected Typed Logical Write w/ 3 Address Fields — File, Element,
Sub-Element
Yes
0x0F
0xAB
SLC-500 Protected Typed Logical Write w/ 4 Address Fields — File, Element,
Sub-Element, Bit Mask
No
0x0F
0x95
Encapsulate Other Protocol message
Yes