Installing a 1336-gm6 board, Installing a 1336-gm6 board -6 – Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 26
![background image](/manuals/578785/26/background.png)
2-6
Installation
Installing a 1336-GM6 Board
Follow these procedures to install a 1336-GM6 board.
Required Tools and Equipment
To install your 1336-GM6 board, you will need the following tools
and equipment:
•
Enhanced DeviceNet communications board (1336-GM6).
•
A kit that includes one grounding wrist strap, four Phillips
mounting screws, four stand-off nylon headers, one 5-pin
connector and one snap-in comm housing with mounting
instructions (supplied with board).
•
#1 Phillips screwdriver.
•
Appropriate cable for the DeviceNet connection. Refer to the
Selecting Cables section below.
Selecting Cables
To connect the Enhanced DeviceNet adapter to the SCANport
product and the DeviceNet network, you must select an appropriate
DeviceNet cable. Use the following information to select appropriate
cables for each connection.
DeviceNet Cables
The 1336-GM6 board comes with one 5-pin connector. A drop line
connects a node, such as an adapter, on the DeviceNet cable system to
the DeviceNet trunk. When selecting a drop line, you need to:
•
Use the 5-pin connector for the cable if you are using a
DeviceNet drop cable configuration.
•
Determine limitations of the trunk and drop cables. Refer to the
following table.
For more information on DeviceNet cables and cable systems, refer to
the DeviceNet Cable System Planning and Installation Manual,
Publication DN-6.7.2.
Data Rates
125 Kbps
250 Kbps
500 Kbps
Thick Trunk Line
500 m (1,640 ft)
250 m (820 ft)
100 m (328 ft)
Thin Trunk Lengths
100 m (328 ft)
100 m (328 ft)
100 m ((328 ft)
Maximum Drop Length
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
Cumulative Drop Budget
156 m (512 ft)
78 m (256 ft)
39 m (128 ft)