Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 103

Enhanced DeviceNet Adapter’s Parameters
B-15
35
Peer Inp Time-out
0.01-180.00 sec
10.00
Yes
No
Determines the time out time. If the adapter
does not receive input from the peer node in this
amount of time, it will do what is selected in
Peer Flt Action (33) parameter.
36
Peer Inp Enable
Off, On
Off
Yes
No
Off = Disables peer input communications.
On = Enables peer input communications.
37
Peer Inp Status
Off
Waiting
Running
Faulted
NA
No
No
Displays the status of the consumed peer input
connection.
38
Peer A Output
Off
Cmd/Ref
DL A Input
DL B Input
DL C Input
DL D Input
DL A Output
DL B Output
DL C Output
DL D Output
Off
Yes
No
Determines the source of peer A output data in
the SCANport product.
Important: This parameter cannot be changed
when the Peer Out Enable (40) parameter is
On.
39
Peer B Output
Off
Cmd/Ref
DL A Input
DL B Input
DL C Input
DL D Input
DL A Output
DL B Output
DL C Output
DL D Output
Off
Yes
No
Determines the source of peer B output data in
the SCANport product.
Important: This parameter cannot be changed
when the Peer Out Enable (40) parameter is
On.
40
Peer Out Enable
On, Off
Off
Yes
No
Off = Disables peer output communications.
On = Enables peer output communications.
41
Peer Out Time
0.01 – 10.00
1.00
Yes
No
Determines the minimum interval of time
between peer transmissions.
42
Peer Out Skip
1 – 16
1
Yes
No
Determines the maximum interval of time
between peer transmissions by multiplying this
value by the value in the Peer Out Time (41)
parameter.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power Cycle
Description
Important: For information on accessing and editing parameters, refer to Chapter 3, Configuring the 1203-GU6 Using a Serial