beautypg.com

Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual

Page 28

background image

2-8

Installation

2. Screw the four stand-off nylon headers into the appropriate

spaces on the drive’s main control board.

Figure 2.6

Mounting the Open Style Communications Board

3. Insert the pins located on the 1336-GM6 into the 14-pin

SCANport header on the drive. The board should sit squarely on
the stand-offs.

4. Using a #1 Phillips screwdriver and the four supplied mounting

screws, screw the board securely into place, being careful not to
overtighten.

5. Attach the wires to the supplied DeviceNet connector.

Important: Refer to Figure 2.6 to verify you’ve wired the connector
correctly to the board. Failure to wire the board correctly may damage
the circuitry or cause the device to not function.

6. Plug the connector into the board receptacle and screw the two

screws into place using a 1/8" flathead screwdriver.

DeviceNet

Connector

Internal SCANport

Connector

Black - V -

Blue - CAN_L

Bare - Shield

White - CAN_H

Red - V+

DeviceNet Status

Module Status

SCANport Status

!

ATTENTION: Static control precautions are required
if you wire the connector when it is already connected
to the adapter. It is not recommended that you do this.
Device malfunction may occur if you do not follow ESD
control procedures. If you are not familiar with static
control procedures, refer to Allen-Bradley Publication
8000-4.5.2, Guarding Against Electrostatic Damage, or
other applicable ESD protection handbooks.

This manual is related to the following products: