Rockwell Automation 1336-GM6 Enhanced DeviceNet Communications Module User Manual
Page 101
Enhanced DeviceNet Adapter’s Parameters
B-13
23
Active I/O Cfg
0 or 1 for each bit
N/A
No
No
Displays what I/O is activated in the adapter.
0 = Off
1 = On
24
M-S Input
0 or 1 for each bit
xxx0, 0001
Yes
Yes
Determines the source of the bits for input.
0 = Peer or other input
1 = Master-Slave input
For more information, refer to the “M-S Input
Parameter Configurations” section in this
chapter.
25
M-S Output
0 or 1 for each bit
xxx0, 0001
Yes
Yes
Determines the source of the bits for output.
0 = Peer or other output
1 = Master-Slave output
For more information, refer to the “M-S Output
Parameter Configurations” section in this
chapter.
26
COS Status Mask
0 or 1 for each bit
0
Yes
No
Provides a mask of the Logic Status word to
define which bits are checked for changes
during COS allocation.
0 = Off (not checked)
1 = On (checked)
Important: Refer to your SCANport product’s
documentation for information on its Logic
Status word.
#
Name
Valid Values/
Settings
Default
Writable
Reset or
Power Cycle
Description
Important: For information on accessing and editing parameters, refer to Chapter 3, Configuring the 1203-GU6 Using a Serial
Connection, or Chapter 4, Configuring the 1203-GU6 or 1336-GM6 Adapter Using RSNetWorx for DeviceNet.
xxx0, 0000
datalink D
datalink C
datalink B
datalink A
Cmd/Stat
xxx0, 0000
datalink D
datalink C
datalink B
datalink A
Cmd/Ref
xxx0, 0000
datalink D
datalink C
datalink B
datalink A
Stat/Fdbk