Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual
Page 21

Chapter 3
Configuration & Interfacing
3–10
BIT
0
0
1
1
Table 3-G.
Function Block Overflow Control, Parameter 517
Send last state (Default)
Zero Inputs
Send max value, pos or neg
None
Action Taken
3 12
0
1
0
1
Overflow Action
BIT
0
0
1
1
None (Default)
Warning
Soft
Hard
Fault Type
5 4
0
1
0
1
Overflow fault Severity
Parameter Description:
Block Output Whole (Par # 316) – This is a fast source parameter which
contains the whole number part of the multiplication. The data can be used
on the Adapter or passed to the Drive by using a Drive configuration link.
Block Output Fractional (Par # 317) – This is a fast source parameter
which contains the fraction number part of the multiplication. The data can
be used on the Adapter or passed to the Drive by using a Drive
configuration link.
Block Input #1 (Par # 506) – A parameter that specifies where this block
gets one of the input values used in the multiplication process. Input data
can come from other functions on this Adapter or from the Drive by using
CA Indirect parameters (refer to Figures 3–3 and 3–4).
Block Input #2 (Par # 507) – A parameter that specifies where this block
gets one of the input values used in the multiplication process. Input data
can come from other functions on this Adapter or from the Drive by using
CA Indirect parameters. Refer to Figures 3–3 and 3–4 for details on input
data.