Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual
Page 141

Table of Contents
8–46
Parameter 576 – [A>ChA DH Rd Wrd1]
Parameter 526 – [B>ChA DH Rd Wrd1]
Use: Channel A Read word 1
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value: 0
Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter determines which of these two
words the DH TP In 1 parameter will receive its data from. The node
address is specified by the DH Rd Nde1 parameter.
Parameter 577 – [A>ChA DH Rd Nde2]
Parameter 527 – [B>ChA DH Rd Nde2]
Use: Channel A Read Station Number 2
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 77
Default Value: 8
Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter specifies which node address the
DH TP In 2 parameter will receive its data from. The node address is
entered in octal so that it corresponds with the node addressing scheme of
DH+. The default value of 8 disables the data transfer.
Parameter 578 – [A>ChA DH Rd Wrd2]
Parameter 528 – [B>ChA DH Rd Wrd2]
Use: Channel A Read word 2
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value: 0
Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter determines which of these two
words the DH TP In 2 parameter will receive its data from. The node
address is specified by the DH Rd Nde2 parameter.