Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual
Page 111

Chapter 8
Reference
8–16
Parameter 561 – [A>Add FB Gain 2]
Parameter 511 – [B>Add FB Gain 2]
Use: Specifies Add input #2 gain value
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: –15.999
Maximum Value: 15.995
Default Value: 0
Description: This parameter specifies the Add input #2 gain value. The
gain value is multiplied by the input #2 data prior to the summation of all
block values.
Parameter 562 – [A>Add FB In 3]
Parameter 512 – [B>Add FB In 3]
Use: Specifies an input to the Add function block
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: B–300/A–400
Maximum Value: B–503/A–553
Default Value: B–320/A–420
Description: This parameter specifies where the Add function block gets
one of its inputs. Input data can come from other functions on this
Adapter or from the Drive by using a CA Indirect parameter linked to the
desired information. A value outside the following ranges disables the
function block input:
CHAN B
CHAN A
300 – 319
400 – 419
350 – 369
450 – 469
500 – 503
550 – 553
Parameter 563 – [A>Add FB Gain 3]
Parameter 513 – [B>Add FB Gain 3]
Use: Specifies Add input #3 gain value
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: –15.999
Maximum Value: 15.995
Default Value: 0
Description: This parameter specifies the Add input #3 gain value. The
gain value is multiplied by the input #3 data prior to the summation of all
block values.