Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual
Page 109
Chapter 8
Reference
8–14
Parameter 555 – [A>Mult1 FB Gain]
Parameter 505 – [B>Mult1 FB Gain]
Use: Specifies Multiply #1 gain value
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: –15.999
Maximum Value: 15.995
Default Value: 0
Description: This parameter specifies the Multiply #1 gain value. The
gain value is multiplied by the input data to obtain the Multiply #1 output
value (Par. #315).
Parameter 556 – [A>Mult2 FB In 1]
Parameter 506 – [B>Mult2 FB In 1]
Use: Determines first input to the Multiply #2 block
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: B–300/A–400
Maximum Value: B–503/A–553
Default Value: B–320/A–420
Description: This parameter specifies where the Multiply #2 function
block gets one of its inputs. Input data can come from other functions on
this Adapter or from the Drive by using a CA Indirect parameter linked to
the desired information. A value outside the following ranges disables the
function block input:
CHAN B
CHAN A
300 – 319
400 – 419
350 – 369
450 – 469
500 – 503
550 – 553
Parameter 557 – [A>Mult2 FB In 2]
Parameter 507 – [B>Mult2 FB In 2]
Use: Determines second input to the Multiply #2 block
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: B–300/A–400
Maximum Value: B–503/A–553
Default Value: B–320/A–420
Description: This parameter specifies where the Multiply #2 function
block gets one of its inputs. Input data can come from other functions on
this Adapter or from the Drive by using a CA Indirect parameter linked to
the desired information. A value outside the following ranges disables
the function block input:
CHAN B
CHAN A
300 – 319
400 – 419
350 – 369
450 – 469
500 – 503
550 – 553