Powermonitor 1000 Data Tables Appendix A
Time of Use Log Results - Real Energy and Demand Parameters
CSP File No.
F31
CIP Instance
24
No. of Elements
12
No. of Words
24
Data Type
Float
Data Access
Read
Time of Use Log Results - Real Energy and Demand
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
0
31201-2
Record Number
1…13
•
•
•
The record number of the log. Record 0 is
always the current record before being
logged.
1
31203-4
Time Stamp Start
Date (yy/mm/dd)
-
•
•
•
The Date this record was started.
2
31205-6
Time Stamp End
Date (yy/mm/dd)
-
•
•
•
The Date this record was ended.
3
31207-8
Off Peak GWh
Net
+/- 0…
9,999,999
•
•
•
Net Off Peak giga watt hours
4
31209-10
Off Peak kWh
Net
+/- 0.000…
999,999
•
•
•
Net Off Peak kilo watt hours
5
31211-12
Off Peak kW
Demand
+/- 0.000…
9,999,999
•
•
•
Off Peak Demand for kilo watts
6
31213-14
Mid Peak GWh
Net
+/- 0…
9,999,999
•
•
•
Net Mid Peak giga watt hours
7
31215-16
Mid Peak kWh
Net
+/- 0.000…
999,999
•
•
•
Net Mid Peak kilowatt hours
8
31217-18
Mid Peak kW
Demand
+/- 0.000…
9,999,999
•
•
•
Mid Peak Demand for kilo watts
9
31219-20
On Peak GWh
Net
+/- 0.000…
9,999,999
•
•
•
Net On Peak giga watt hours
10
31221-22
On Peak kWh Net +/- 0…
999,999
•
•
•
Net On Peak kilo watt hours
11
31223-24
On Peak kW
Demand
+/- 0.000…
9,999,999
•
•
On Peak Demand for kilo watts