beautypg.com

Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 50

background image

50

Publication 1408-UM001B-EN-P - May 2008

Appendix A Powermonitor 1000 Data Tables

17

40135-36

Forced
Demand
Sync Delay

10 s

0…900 s

When the power monitor is configured for
external demand control the unit delays
for xxx seconds after the expected control
pulse has not been received. The demand
period starts over and a record is recorded
in the status log.

0 = Wait forever
1…900 = Wait this many seconds before
starting a new demand period.

This setting becomes active when the
demand interval is set from -1…-99
minutes.

18

40137-38

Unit Error
Action

1

0…1

This parameter determines the action
when a unit error occurs.

0 = Halt on error and make status LED
solid red
1 = Reset power monitor hardware.

19

40139-40

Software
Error Log Full
Action

1

0…1

This parameter determines the action
when a firmware failure is detected and
the error log is full.

0 = Halt on error and wait for clear log
command, also make status LED solid red
1 = Perform a firmware reset.

20

40141-42

Reserved

0

0

Reserved for future use.

21

40143-44

Reserved

0

0

Reserved for future use.

Advanced Configuration

Element
No.

Modbus
Address
Range

Element
Name

Default
Value

Range

TR1

TR2

EM1

EM2

EM3

Description