Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 50
50
Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
17
40135-36
Forced
Demand
Sync Delay
10 s
0…900 s
•
•
When the power monitor is configured for
external demand control the unit delays
for xxx seconds after the expected control
pulse has not been received. The demand
period starts over and a record is recorded
in the status log.
0 = Wait forever
1…900 = Wait this many seconds before
starting a new demand period.
This setting becomes active when the
demand interval is set from -1…-99
minutes.
18
40137-38
Unit Error
Action
1
0…1
•
•
•
•
•
This parameter determines the action
when a unit error occurs.
0 = Halt on error and make status LED
solid red
1 = Reset power monitor hardware.
19
40139-40
Software
Error Log Full
Action
1
0…1
•
•
•
•
•
This parameter determines the action
when a firmware failure is detected and
the error log is full.
0 = Halt on error and wait for clear log
command, also make status LED solid red
1 = Perform a firmware reset.
20
40141-42
Reserved
0
0
•
•
•
•
•
Reserved for future use.
21
40143-44
Reserved
0
0
•
•
•
•
•
Reserved for future use.
Advanced Configuration
Element
No.
Modbus
Address
Range
Element
Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description