Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 52

52
Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
5
40206
Data Format
0
0…2
(2 for
DH485)
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
6
40207
Inter Character
Timeout
0
0…
6553
Specifies the minimum delay between characters that indicates the
end of a message packet for Modbus protocol. 0 = 3.5 character
times in default. The unit is ms.
8
40208
Maximum Node
Address
3
1…31
Specifies the maximum node address on a DH485 network.
9
40209
Reserved
0
0
Reserved for future use.
Serial RS-485 Port Configuration
Element
No.
Modbus
Address
Element Name
Default
Value
Range
Description
Ethernet Configuration Parameters
CSP File No.
N13
CIP Instance
6
No. of Elements
23
No. of Words
23
Data Type
Integer
Data Access
Read/Write
Ethernet Configuration
Element
No.
Modbus
Address
Element Name
Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40301
Password
0
0…9999
• •
• • •
When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
1
40302
IP Address Byte a
(aaa.xxx.xxx.xxx)
192
0…255
• •
• • •
The 1st Octet of the Static IP Address.
2
40303
IP Address Byte b
(xxx.bbb.xxx.xxx)
168
0…255
• •
• • •
The 2nd Octet of the Static IP Address.
3
40304
IP Address Byte c
(xxx.xxx.ccc.xxx)
254
0…255
• •
• • •
The 3rd Octet of the Static IP Address.
4
40305
IP Address Byte d
(xxx.xxx.ddd.xxx)
Unit ID
0…255
• •
• • •
The 4th Octet of the Static IP Address.