Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 61
Publication 1408-UM001B-EN-P - May 2008
61
Powermonitor 1000 Data Tables Appendix A
Command Table
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0
40601-2
Password
0
0…9999
•
•
•
•
•
When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
1
40603-4
Command Word
1
0
0…32
•
•
•
•
•
These commands can be sent to the
power monitor. When using the optional
elements the command table must be
sent complete with all elements present.
If the single password table is used to
gain access to configuration items then
the command can be sent alone without
optional settings. The command options
are:
0 = No Action
1 = Set kWh Register
2 = Set kVARh Register
3 = Set kVAh Register
4 = Clear All Energy Registers
5 = Set Status 1 Count
6 = Set Status 2 Count
7 = Clear Energy Log
8 = Force KYZ Output On
9 = Force KYZ Output Off
10 = Remove Force from KYZ
11 = Restore Factory Defaults
12 = Perform Wiring Diagnostics
13 = Reset power monitor System
14…32 = Reserved
If a command is received that is not
supported by your catalog number the
command will be ignored.
2
40605-6
Command Word
2
0
0…32
•
•
•
•
•
0 = No Action
1 = Clear Min/Max Records
2 = Store and clear current Load Factor
Record
3 = Clear Load Factor Log
4 = Store and clear current TOU Record
5 = Clear TOU Log
6 = Clear Error Log command
7 = Troubleshooting Mode Enable
8…32 = Reserved.
If a command is received that is not
supported by your catalog number the
command will be ignored.