beautypg.com

Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 61

background image

Publication 1408-UM001B-EN-P - May 2008

61

Powermonitor 1000 Data Tables Appendix A

Command Table

Element
No.

Modbus
Address

Element Name Default

Value

Range

TR1

TR2

EM1

EM2

EM3

Description

0

40601-2

Password

0

0…9999

When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.

1

40603-4

Command Word
1

0

0…32

These commands can be sent to the
power monitor. When using the optional
elements the command table must be
sent complete with all elements present.
If the single password table is used to
gain access to configuration items then
the command can be sent alone without
optional settings. The command options
are:

0 = No Action
1 = Set kWh Register
2 = Set kVARh Register
3 = Set kVAh Register
4 = Clear All Energy Registers
5 = Set Status 1 Count
6 = Set Status 2 Count
7 = Clear Energy Log
8 = Force KYZ Output On
9 = Force KYZ Output Off
10 = Remove Force from KYZ
11 = Restore Factory Defaults
12 = Perform Wiring Diagnostics
13 = Reset power monitor System
14…32 = Reserved
If a command is received that is not
supported by your catalog number the
command will be ignored.

2

40605-6

Command Word
2

0

0…32

0 = No Action
1 = Clear Min/Max Records
2 = Store and clear current Load Factor
Record
3 = Clear Load Factor Log
4 = Store and clear current TOU Record
5 = Clear TOU Log
6 = Clear Error Log command
7 = Troubleshooting Mode Enable
8…32 = Reserved.
If a command is received that is not
supported by your catalog number the
command will be ignored.

This manual is related to the following products: