Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 71
Publication 1408-UM001B-EN-P - May 2008
71
Powermonitor 1000 Data Tables Appendix A
6
30213-14
L3-N Volts
0.000…9,999,999
•
•
•
Phase 3 scaled RMS Voltage
7
30215-16
Average L-N Volts
0.000…9,999,999
•
•
•
Averaged RMS Voltage
8
30217-18
L1-L2 Volts
0.000…9,999,999
•
•
•
Line 1 to Line 2 Volts
9
30219-20
L2-L3 Volts
0.000…9,999,999
•
•
•
Line 2 to Line 3 Volts
10
30221-22
L3-L1 Volts
0.000…9,999,999
•
•
•
Line 3 to Line 1 Volts
11
30223-24
Average L-L Volts
0.000…9,999,999
•
•
•
Average Line to Line Volts
12
30225-26
Frequency
40.0 Hz…70.0 Hz
•
•
•
Last frequency reading.
13
30227-28
Percent Current
Unbalance
0.0…100.0
•
•
•
Percent maximum deviation from
Ave. / Ave.
14
30229-30
Percent Voltage
Unbalance
0.0…100.0
•
•
•
Percent Maximum deviation from
Ave. / Ave.
15
30231-32
Metering Iteration
0…9,999,999
•
•
•
Increments by 1 for each new
metering calculation.
Volts, Amps, Frequency Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
Power Results Parameters
CSP File No.
F22
CIP Instance
15
No. of Elements
17
No. of Words
34
Data Type
Float
Data Access
Read
Power Results
Element
No.
Modbus
Address
Element Name
Range
TR1
TR2
EM1
EM2
EM3
Description
0
30301-2
L1 True Power
Factor
-100.0…+100.0
•
•
Percent ratio between power and
apparent power. The value is
signed to (+) leading and (-)
lagging.
1
30303-4
L2 True Power
Factor
-100.0…+100.0
•
•
2
30305-6
L3 True Power
Factor
-100.0…+100.0
•
•
3
30307-8
3 Phase True
Power Factor
-100.0…+100.0
•
•
4
30309-10
L1 kWatts
+/- 0.000…9,999,999
•
•
Line 1 kWatts
5
30311-12
L2 kWatts
+/- 0.000…9,999,999
•
•
Line 2 kWatts