Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual
Page 85
![background image](/manuals/578271/85/background.png)
Publication 1408-UM001B-EN-P - May 2008
85
Powermonitor 1000 Data Tables Appendix A
33
kVAR Demand
•
34
kVA Demand
•
35
PF Demand
•
Load Factor Log Results Parameters
CSP File No.
F30
CIP Instance
23
No. of Elements
14
No. of Words
28
Data Type
Float
Data Access
Read
Min/Max Parameter List
No.
Parameter
TR1
TR2
EM3
Load Factor Log Results
Element
No.
Modbus
Address
Element Name
Range
TR
1
TR
2
EM
1
EM
2
EM
3
Description
0
31101-2
Record Number
1…13
•
•
The record number of this data.
1
31103-4
End Date
yy/mm/dd
-
•
•
The date that this record was stored.
2
31105-6
Elapsed Time
0.000…
9,999,999
•
•
Amount of time (in hours) that has
elapsed since the last clear of the peak
and average values. Updated at the end
of each demand interval.
3
31107-8
Peak Demand
kWatts
+/-
0.000…9,999,
999
•
•
The largest magnitude demand for
kwatts that occurred over all of the
demand intervals since the last clear
command or auto-clear day.
4
31109-10
Average Demand
kWatts
+/-
0.000…9,999,
999
•
•
A running average of demand for
kwatts from the end of each demand
period since the last clear command or
auto-clear day.
5
31111-12
Load Factor
kWatts
0…100%
•
•
Average Demand kW / Peak Demand
kW. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.