Chapter 5 SCADA Applications
In this example, the User Configured Read Instance F9, element
8, in the OPC topic EM3_LAB is selected.
3. Click OK and start viewing data.
User-configured Data Table
The 1408-EM3 model provides a user configured data table. You may
select the 16 floating-point parameters that comprise this table. Your
application may read this table as connected input instance 1, or as
CSP file F9 using explicit messaging.
Setup
You must use serial or Ethernet network communication to set up and
read the user configured data table.
To set up the user configured table, using explicit messaging, write a
new configuration to the User Configured Table Setup table.
See
page 92
for the content, default parameters and addressing details
of the setup table.
list the available selections for the
parameters.